Automated Fault Location, Isolation, and Service Restoration (FLIR/FLISR) creates a 'self-healing' distribution grid. When a tree hits a power line, FLIR software uses smart switches to instantly identify the exact fault location, isolate the damaged block, and automatically reroute power from adjacent neighborhoods to restore electricity to 80% of customers within 30 seconds.
Historically, a fault tripped a substation breaker, blacking out 5,000 homes. A truck drove the line for hours to find the tree. FLISR utilizes intelligent electronic devices (IEDs) and motorized reclosers stationed along the feeder. When a fault occurs, the reclosers communicate peer-to-peer (via IEC 61850 GOOSE messaging) or via a centralized ADMS. They triangulate the fault based on fault current detection, lock out the specific broken segment, and close tie-switches to backfeed the healthy segments from parallel circuits.
Fault Detection (Location)
Relays detect a massive overcurrent spike and record the directional flow of the fault current to pinpoint the damage between two specific switches.
Switching Sequence (Isolation)
Motorized switches on either side of the fault open automatically, physically isolating the downed wire.
Load Flow Check (Restoration)
The ADMS verifies that backfeeding from an adjacent feeder won't overload that neighboring circuit, then closes the tie-switch to restore power.
- Telecom reliability: FLISR completely fails if the cellular or radio network connecting the pole-mounted switches drops out during a storm.
- Load masking by solar: High penetration of residential solar can confuse the fault current detectors, causing the FLISR algorithm to execute incorrect switching sequences.