Grid-Following (GFL) inverters represent over 95% of deployed solar and wind power conversion systems. They act as current sources that track the grid's existing voltage and frequency using a Phase-Locked Loop (PLL), injecting active and reactive power as commanded.
A GFL inverter cannot establish a grid on its own; it requires a strong external voltage reference. The Phase-Locked Loop (PLL) continuously measures the grid voltage phase angle to synchronize current injection. In very weak grids where the Short Circuit Ratio (SCR) is low, the PLL can lose synchronization, leading to instability.
Phase-Locked Loop (PLL) Sync
The inverter measures the Point of Common Coupling (PCC) voltage and extracts the phase angle to align its output current.
Current Injection
Active and reactive power setpoints are converted into current references. The inverter injects current exactly in phase (for active power) with the grid voltage.
Anti-Islanding Protection
Active and passive anti-islanding algorithms detect loss of grid and shut down the inverter within milliseconds to prevent backfeeding.
Fault Ride-Through (FRT)
During voltage sags, the inverter halts active power and injects reactive current to support grid voltage recovery per grid codes.
- Weak Grid Instability: At SCR < 3, the PLL struggles to track the highly distorted voltage, causing control loop hunting and tripping.
- Lack of Inertia: GFL inverters provide zero physical inertia, accelerating Rate of Change of Frequency (RoCoF) during generation loss events.
- Anti-Islanding Conflict: Nuisance tripping can occur during minor grid disturbances if anti-islanding thresholds are too sensitive.